Controller · Mitsubishi Electric

Connect Mitsubishi Electric M8 series (M800 / M80 / E80)

M800, M80 and E80 provide Ethernet, EZSocket, the Custom API Library and an SLMP server as standard. OPC UA and MTConnect run on a PC with Mitsubishi's NC Machine Tool Connector or MTConnect Adapter. Network settings are made on the IoT-Friendly Setup screen ([PRM] → [IoT-F]).

At a glance

Standard interfacesEthernet, EZSocket, Custom API, SLMP
OPC UANC Machine Tool Connector (PC)
MTConnectMTConnect Adapter (PC)
Settings[PRM] → [IoT-F]
Port labelCNLAN

Connection paths

MTConnect AdapterAlternative

PLC devices via third-party driverAlternative

E-stop, overrides, spindle, part count and tool life from documented PLC devices

Licences and options

ItemOption / part numberPaid?Note
NC Machine Tool ConnectorLicence keyPaid
MES Interface LibraryOption on M800W/S, standard on M80WDepends

Ports

PortProtocolNote
683TCPEZSocket default used by third-party drivers (not in Mitsubishi documents)
4840TCPNC Machine Tool Connector OPC UA

Software versions

  • MTConnect Adapter NC type 1: M800W, M800S, M80W, M80, E80, C80 and the M8V models

Data you can read

  • Programs and files: read, write, upload, download (Custom API / EZSocket)
  • Coordinates, alarms and diagnostic information
  • NC data: tool data, variables; PLC device values
  • Through the MTConnect adapter: axis position and load, spindle load, actual and commanded speed, spindle temperature, availability, emergency stop, NC and PLC alarms, power-on and operating time, cycle time, feed rates, block, mode, execution, line, M-codes, part count, program and sequence numbers, tool number, power consumption
  • PLC devices (example): R69 emergency stop, R2500 feed override, R7008 spindle override, R6506 actual spindle speed, R6525 spindle load, R606–607 part count, R11824–11833 tool group, number, usage and life

Setting it up

  1. Enable Ethernet on the CNCM800/M80/M850: [PRM] → [>] → [IoT-F] "IoT-Friendly Setup": set IP address, subnet, gateway; leave the port field at 0. Older M70/M700: parameters #1925 (Ethernet enable = 1), #1926 IP, #1927 subnet, #1928 gateway. Power-cycle the whole machine.
  2. Use the CNLAN portThe built-in Ethernet connector is labelled CNLAN.
  3. Choose the PC softwareFor MTConnect: Mitsubishi MTConnect Adapter + MTConnect Data Collector (Edgecross) on a 64-bit Windows 10 industrial PC. For OPC UA: NC Machine Tool Connector, a Windows service that serves OPC UA with the OPC UA for Machine Tools (umati) model.
  4. Licence the PC softwareThe MTConnect Data Collector needs a product ID; NC Machine Tool Connector installs with a licence key.
  5. Test one machineRead mode, execution state and part count before adding the full tag list.

Troubleshooting

SymptomLikely causeFix
Machine will not boot after network changeIP entered in an HMI IP fieldNever enter addresses in the HMI IP fields (integrator warning: it can brick the machine). Use only the NC Ethernet parameters.
MTConnect values show UnavailableLink to the NC dropped or collection interval shorter than the agent intervalCheck the cable and set the collection interval equal to or longer than the agent interval.
Adapter makes the M7 control alarmNC-MAIN software below the minimumUpdate the NCU firmware; integrator guidance lists minimum NC-MAIN versions per machine type.

Traps to avoid

  • FTP high-speed program server mode is not available on M8.

Connectors that support this control

ProductVendorTypeOutputs
NC Machine Tool ConnectorMitsubishi ElectricControl or machine makerOPC UA (OPC UA for Machine Tools), MQTT
MTConnect Adapter + Data CollectorMitsubishi ElectricControl or machine makerMTConnect
DeviceXPlorer OPC ServerTakebishi (ICONICS)OPC server / driverOPC UA, OPC DA, MQTT, HTTP
Neuron / NeuronEXEMQXEdge platformMQTT, Sparkplug B
WebAccess/CNCAdvantechMonitoring softwareOPC UA/DA, Modbus, REST
MachineMetrics EdgeMachineMetricsMonitoring softwareCloud

CNC connector directory →

Sources

Facts on this page come from these documents, opened on 27 October 2026.

  1. Mitsubishi Electric — M800/M80/E80/C80 Specifications Manual (Function) IB-1501505
  2. Mitsubishi Electric — NC Machine Tool Connector manual IB-1501634
  3. Mitsubishi Electric — MTConnect Data Collector manual IB-1501538
  4. Mitsubishi Electric — Custom API Library
  5. MachineMetrics support — Mitsubishi M80/M800
  6. EMQX Neuron — Mitsubishi CNC driver

Last verified 27 October 2026 against vendor documentation. OPC UA Connect is an educational resource published by TEEPTRAK; it is not affiliated with the OPC Foundation, the MTConnect Institute or any control maker.