Controller · Siemens

Connect SINUMERIK ONE

SINUMERIK ONE runs OPC UA server versions 3.1 to 4.2 depending on the Operate version (6.14 to 6.24). The Access MyMachine /OPC UA licence for ONE is an electronic licence: Siemens lists 6FC5800-0BP82-0YB0. The server is based on OPC UA 1.04 and adds an "OPC UA Advanced" layer (machine state, tool management, production dialog). Newer security policies (Aes128Sha256RsaOaep, Aes256Sha256RsaPss) are available; Basic128Rsa15 and Basic256 are deprecated.

At a glance

Native protocolOPC UA server 3.1 to 4.2
Licence6FC5800-0BP82-0YB0 (electronic)
PortTCP 4840
SecurityBasic256Sha256 on by default; AES policies available
ExtrasOPC UA Advanced, RegisterAdvHost
umatiNot mentioned in the ONE OPC UA manual

Connection paths

IBH Link UAAlternative

Lists SINUMERIK ONE support and an OPC 40502 CNC model.

Industrial Edge / Manage MyMachinesVendor product

ONE NCU 1740/1750/1760, Operate 6.13 onward depending on app

Licences and options

ItemOption / part numberPaid?Note
Access MyMachine /OPC UA (ONE)6FC5800-0BP82-0YB0PaidElectronic licence; the ONE manual also prints 6FC5800-0BP67-0Yx0

Ports

PortProtocolNote
4840TCPOPC UA

Software versions

  • OPC UA 4.2 ↔ Operate 6.15, 6.20 to 6.24
  • OPC UA 4.1 SP1 ↔ 6.15 to 6.23
  • OPC UA 4.0 / 4.0 SP1 ↔ 6.15, 6.20, 6.21
  • OPC UA 3.1 SP1 ↔ 6.15; 3.1 ↔ 6.14

Data you can read

  • Channel state: execution state, operating mode, active program name, block, line
  • Spindle: rotating, speed, load; feed rate and override
  • Alarms: event-based NC, PLC and HMI alarms with multilingual texts (needs the AlarmRead right)
  • R parameters, global user data (GUD) and NC variables by path, for example /Channel/Parameter/R[u1,10]
  • PLC data: /Plc/MB6, /Plc/DB5.DBW2, arrays such as /Plc/DB2.DBD0:REAL[10] (828D: customer DBs from DB9000 only)
  • Tools: tool data, cutting edges, magazine; methods to create and delete tools and cutting edges
  • Part counters (actual and total parts) and program selection (Select/Deselect methods with the ApWrite right)
  • OPC UA Advanced: machine state, tool management, production dialog, workpiece carrier, Tool Ident Connection

Setting it up

  1. Check the licence and software versionAccess MyMachine /OPC UA must be licensed and activated: order number 6FC5800-0AP67-0YB0 for 840D sl and 828D. Check the CNC software version against the compatibility table below before you order.
  2. Use the right network interface828D: X130 (company network). 840D sl with thin client: X120 and X130 on the NCU. 840D sl with PCU or IPC: the server is reachable on eth1 and eth2 of the PC, not on X120/X130. Do not change the 192.168.214.x and 192.168.215.x system networks.
  3. Raise the access levelEnter the Manufacturer access level so the commissioning screens are available.
  4. Activate the serverStartup (Commissioning) > Network > OPC UA > Setting > Change. Choose the network (company, system or service), confirm IP address and port 4840, tick "Activate OPC UA", OK.
  5. Create a user and rightsAnonymous access is off by default and should stay off. Create a user with a strong password (8 or more characters, mixed case, digits, special characters) and give it only the rights it needs, for example StateRead, ToolRead, AlarmRead.
  6. RestartHardware restart of the NCU or PPU; on a PCU 50 or IPC, restart Operate.
  7. Exchange certificatesStartup > Network > OPC UA > Certificates. The server certificate is generated at first start (20-year validity). Import the client certificate (.der) and trust the HMI certificate on the client side. Switch off automatic certificate acceptance once commissioning is done.
  8. Verify with a generic clientConnect with UaExpert to opc.tcp://<HMI-IP>:4840 using Basic256Sha256 Sign & Encrypt, browse, read a channel state, then hand over to the production client.

Troubleshooting

SymptomLikely causeFix
BadCertificateTimeInvalidSystem time wrong on the control or the clientSet the clock on both sides (NTP where possible), then reconnect.
BadSecurityChecksFailedClient certificate not trusted by the serverMove the client certificate to the trusted list under Startup > Network > OPC UA > Certificates.
Endpoint not reachable on 840D sl with PCUClient is dialling X120/X130With a PCU or IPC the server listens on eth1/eth2 of the PC; open TCP 4840 in the PC firewall.
Login works, every read is deniedNew users have no rightsGrant the needed rights (StateRead, AlarmRead, ToolRead, PlcRead…) with the admin user.
828D cannot read a PLC data block828D exposes customer data blocks from DB9000 onlyAsk the PLC programmer to copy the values into a DB at or above DB9000.
Security None endpoint missingOnly 256-bit policies are active by defaultKeep it that way in production; enable None only temporarily for a reachability test if your site policy allows it.

Traps to avoid

  • Basic128Rsa15 and Basic256 are deprecated and off by default; clients limited to these policies will not connect.
  • Passwords: 8 to 120 characters.

Connectors that support this control

ProductVendorTypeOutputs
IBH Link UAIBHsoftecGatewayOPC UA (incl. OPC 40502 CNC model), MQTT Sparkplug B
dataFEED OPC Server CNCSoftingOPC server / driverOPC DA; optional OPC UA 1.04, MQTT, REST
Manage MyMachinesSiemensControl or machine makerCloud (Insights Hub)
Industrial Edge for Machine ToolsSiemensControl or machine makerREST, MQTT
ConnectwareCybusEdge platformMQTT, OPC UA server
StateMonitorHEIDENHAINControl or machine makerERP/MES job interface

CNC connector directory →

Not published by the vendor. We could not find these in vendor documentation. Ask the control or machine maker before you rely on them.
  • Whether SINUMERIK ONE ships an OPC 40501 (umati) information model: not in the ONE OPC UA manual; VDW lists Siemens as a supporting control supplier

Questions engineers ask

Which OPC UA version runs on SINUMERIK ONE?

From 3.1 (Operate 6.14) to 4.2 (Operate 6.15 and 6.20 to 6.24).

Sources

Facts on this page come from these documents, opened on 27 October 2026.

  1. Siemens — SINUMERIK ONE OPC UA configuration manual (07/2024)
  2. Siemens Industry Mall — 6FC5800-0BP82-0YB0
  3. IBHsoftec — IBH Link UA
  4. Siemens — Manage MyMachines system requirements
  5. Siemens — Analyze MyMachine /Condition installation manual (10/2023)
  6. VDW — control suppliers supporting umati

Last verified 27 October 2026 against vendor documentation. OPC UA Connect is an educational resource published by TEEPTRAK; it is not affiliated with the OPC Foundation, the MTConnect Institute or any control maker.