Controller · Siemens

Connect SINUMERIK 828D

SINUMERIK 828D supports the Access MyMachine /OPC UA server (6FC5800-0AP67-0YB0) on interface X130, port 4840. PLC access through OPC UA is limited to customer data blocks from DB9000. Version compatibility follows the same table as the 840D sl; Manage MyMachines lists 828D from software 4.5 SP4.

At a glance

Native protocolOPC UA server (licensed)
Licence6FC5800-0AP67-0YB0
PortTCP 4840
InterfaceX130
PLC accessCustomer DBs from DB9000 only
GatewaysLitmus lists no 828D driver; S7 gateways mainly target 840D

Connection paths

Siemens Manage MyMachinesVendor product

828D with Integrate client 2.0.x to 4.0.x depending on software version.

Licences and options

ItemOption / part numberPaid?Note
Access MyMachine /OPC UA6FC5800-0AP67-0YB0Paid

Ports

PortProtocolNote
4840TCPOPC UA on X130

Software versions

  • Same OPC UA server versions as 840D sl (4.5 / 4.07 / 4.08 / 4.92)
  • Manage MyMachines: 4.5 SP4–SP6 (PPU 2x1.3), 4.7 SP2–SP7 and 4.8 SP4–SP7, 4.94–4.95 SP4
  • The SINUMERIK ONE OPC UA manual covers 828D PPU "PU.5" only; older PPU types use the 840D sl/828D manual

Data you can read

  • Channel state: execution state, operating mode, active program name, block, line
  • Spindle: rotating, speed, load; feed rate and override
  • Alarms: event-based NC, PLC and HMI alarms with multilingual texts (needs the AlarmRead right)
  • R parameters, global user data (GUD) and NC variables by path, for example /Channel/Parameter/R[u1,10]
  • PLC data: /Plc/MB6, /Plc/DB5.DBW2, arrays such as /Plc/DB2.DBD0:REAL[10] (828D: customer DBs from DB9000 only)
  • Tools: tool data, cutting edges, magazine; methods to create and delete tools and cutting edges
  • Part counters (actual and total parts) and program selection (Select/Deselect methods with the ApWrite right)

Setting it up

  1. Check the licence and software versionAccess MyMachine /OPC UA must be licensed and activated: order number 6FC5800-0AP67-0YB0 for 840D sl and 828D. Check the CNC software version against the compatibility table below before you order.
  2. Use the right network interface828D: X130 (company network). 840D sl with thin client: X120 and X130 on the NCU. 840D sl with PCU or IPC: the server is reachable on eth1 and eth2 of the PC, not on X120/X130. Do not change the 192.168.214.x and 192.168.215.x system networks.
  3. Raise the access levelEnter the Manufacturer access level so the commissioning screens are available.
  4. Activate the serverStartup (Commissioning) > Network > OPC UA > Setting > Change. Choose the network (company, system or service), confirm IP address and port 4840, tick "Activate OPC UA", OK.
  5. Create a user and rightsAnonymous access is off by default and should stay off. Create a user with a strong password (8 or more characters, mixed case, digits, special characters) and give it only the rights it needs, for example StateRead, ToolRead, AlarmRead.
  6. RestartHardware restart of the NCU or PPU; on a PCU 50 or IPC, restart Operate.
  7. Exchange certificatesStartup > Network > OPC UA > Certificates. The server certificate is generated at first start (20-year validity). Import the client certificate (.der) and trust the HMI certificate on the client side. Switch off automatic certificate acceptance once commissioning is done.
  8. Verify with a generic clientConnect with UaExpert to opc.tcp://<HMI-IP>:4840 using Basic256Sha256 Sign & Encrypt, browse, read a channel state, then hand over to the production client.

Troubleshooting

SymptomLikely causeFix
BadCertificateTimeInvalidSystem time wrong on the control or the clientSet the clock on both sides (NTP where possible), then reconnect.
BadSecurityChecksFailedClient certificate not trusted by the serverMove the client certificate to the trusted list under Startup > Network > OPC UA > Certificates.
Endpoint not reachable on 840D sl with PCUClient is dialling X120/X130With a PCU or IPC the server listens on eth1/eth2 of the PC; open TCP 4840 in the PC firewall.
Login works, every read is deniedNew users have no rightsGrant the needed rights (StateRead, AlarmRead, ToolRead, PlcRead…) with the admin user.
828D cannot read a PLC data block828D exposes customer data blocks from DB9000 onlyAsk the PLC programmer to copy the values into a DB at or above DB9000.
Security None endpoint missingOnly 256-bit policies are active by defaultKeep it that way in production; enable None only temporarily for a reachability test if your site policy allows it.

Traps to avoid

  • Only DB9000 and above are reachable for PLC data: plan the PLC interface with the builder.
  • 828D V4.5 has its own exceptions in the configuration dialog; follow the manual chapter for that version.

Connectors that support this control

ProductVendorTypeOutputs
Manage MyMachinesSiemensControl or machine makerCloud (Insights Hub)
ConnectwareCybusEdge platformMQTT, OPC UA server
WebAccess/CNCAdvantechMonitoring softwareOPC UA/DA, Modbus, REST
StateMonitorHEIDENHAINControl or machine makerERP/MES job interface
FactoryWiz MonitoringFactoryWizMonitoring software—
Predator MDCPredator SoftwareMonitoring softwareSQL / MES / ERP

CNC connector directory →

Not published by the vendor. We could not find these in vendor documentation. Ask the control or machine maker before you rely on them.
  • Maximum client count

Questions engineers ask

Does the 828D have OPC UA?

Yes, with the Access MyMachine /OPC UA licence, on X130, port 4840.

Sources

Facts on this page come from these documents, opened on 27 October 2026.

  1. Siemens — SINUMERIK 840D sl/828D Access MyMachine/OPC UA configuration manual (08/2019)
  2. Siemens — SINUMERIK ONE OPC UA configuration manual (07/2024)
  3. MachineMetrics support — SINUMERIK OPC UA connectivity
  4. Siemens — Manage MyMachines system requirements
  5. Litmus Edge — Siemens drivers

Last verified 27 October 2026 against vendor documentation. OPC UA Connect is an educational resource published by TEEPTRAK; it is not affiliated with the OPC Foundation, the MTConnect Institute or any control maker.